Unit Master

This picture blow is basic power plant control where the load is controlled by the boiler (Boiler Master) and the main steam pressure is controlled by the turbine (Turbine Master).

























The highest hierarchy is Load frequency Control (LFC). If LFC is selected, the power station load rump up or down is based on fluctuating of the frequency grid. In the steam power station usually limitation of load compensation up or down from load set is 5 MW to stabilize the frequency.
Click here for more information about LFC in bahasa

Below LFC is Automatic Load Regulator (ALR) Control. The ALR is set by power station operator, and the frequency grid is controlled by dispatcher. When frequency increase, the dispatcher order to power station operator to reduce the load, and also vies versa.


Speed control, load control and pressure control is selected base on priority.
During start-up, the priority is turbine speed, whatever the load and pressure. The speed is controlled by governor and after synchronized, the governor setter automatically follows to the value a little bit lower than a load limit set value.

Load control is the priority the MW output, this controls selected when normal operation. The load limit setter automatically follows to the value a little bit higher than the flow demand. The turbine speed or frequency is controlled by dispatcher by ordered power stations to rump up or down the load.

Pressure control is automatically selected when the unit got trouble like unit run back or unit goes to house load after load rejection. The priority is the main stem pressure whatever load output to maintain the stabilization of unit. It means the load is followed how much the main steam pressure. The turbine speed or frequency is still under controlled by dispatcher.

For Run Back even to 50% load, because one of two main equipments trip likes circulating water pump, boiler feed pump, primary air fan, forced drive fan, induced drive fan and air heater. Two of five pulverizers will automatically trip and mode auto select to turbine follow mode.

The standard mode is Coordinate Mode. If load set is change, unit control will rump up or down the fuel flow, then delay to turbine load rump up or down.

If the turbine master does not follow the request of unit control, it will switch over to boiler follow mode. It means turbine master is on trouble and set to manual, and boiler is following what ever turbine master set.
Example: External set point for turbine load is not active.

If the boiler master does not follow the request of unit control, it will switch over to turbine follow mode. It means boiler master is on trouble and set to manual, and turbine is following what ever boiler master set.
Example: All feeders set manually.
Exception: The initiation of unit run back will result in an automatic switch over to turbine follow.

During start up and shut down the unit, turbine and boiler are controlled separately by operator is called base mode.



Boiler Master.























Turbine Master.
























Unit Master
























Also visit http://idpowerstation.blogspot.com/2012/04/energy-pu-mass-compensation.html

12 comments:

  1. Hello to every one, the contents existing at this web site are
    actually amazing for people knowledge, well,
    keep up the nice work fellows.

    Feel free to surf to my blog post erc vietnam

    ReplyDelete
  2. This paragraph is in fact a pleasant one it helps new internet people, who are wishing ffor blogging.



    My web site ... clash of clans - Www.stezhky.org.ua -

    ReplyDelete
  3. Hey There. I found your blog using msn. This is an extremely well written article.
    I'll make sure to bookmark it and come back to read more of your useful
    information. Thanks for the post. I'll certainly comeback.


    my website ... service air conditioner Dallas

    ReplyDelete
  4. Heya i am for the first time here. I came across this board and
    I find It truly useful & it helped me out a lot.
    I hope to give something back and aid others like you helped me.


    My web site ... weight loss

    ReplyDelete
  5. it's terribly simple to finding U.S. as we have a tendency to area unit at your town or nearest places. simply keep in mind U.S. and that we can money your check terribly short amount with a awfully low value.

    ReplyDelete
  6. Attempt and pay off your advance as fast as could be expected under the circumstances. Paying in portions may be advantageous, yet you'll be paying tremendous expenses for the benefit. A decent approach to pay it down quick is to pay back more than you owe every month.

    ReplyDelete
  7. I precisely wanted to say thanks once more. I do not know what I could possibly have taken care of without those creative ideas shown by you on this subject. It had become an absolute alarming concern in my view, but finding out a well-written strategy you dealt with that forced me to weep with gladness. Now i'm grateful for your advice and even sincerely hope you really know what a great job your are providing training others through your web page. I'm certain you've never met any of us.
    Steam boiler

    ReplyDelete
  8. Hello there, You've done a fantastic job. I will certainly digg it and personally suggest to my friends. I'm confident they will be benefited from this web site.
    Boiler sizes industrial

    ReplyDelete
  9. Wonderful blog! I found it while surfing around on Yahoo News. Do you have any suggestions on how to get listed in Yahoo News? I've been trying for a while but I never seem to get there! Cheers
    1000 Kg/h steam boiler

    ReplyDelete
  10. fantastic issues altogether, you just won a logo new reader. What would you recommend about your post that you just made a few days ago? Any certain?
    1000 Kg/h steam boiler

    ReplyDelete
  11. Admiring the time and effort you put into your blog and detailed information you provide. It's nice to come across a blog every once in a while that isn't the same old rehashed material. Great read! I've saved your site and I'm adding your RSS feeds to my Google account.
    1000 Kg/h steam boiler

    ReplyDelete
  12. Hey I am so delighted I found your website, I really found you by mistake, while I was browsing on Askjeeve for something else, Nonetheless I am here now and would just like to say thank you for a tremendous post and a all round interesting blog (I also love the theme/design), I don’t have time to look over it all at the moment but I have bookmarked it and also added your RSS feeds, so when I have time I will be back to read a great deal more, Please do keep up the great work.
    Boiler sizes industrial

    ReplyDelete